3-Phase Power & Motor Sizing Calculator

Calculate required amperage, wire size (AWG), and breaker size for 3-phase industrial motors. Includes voltage drop check for long cable runs. Based on NEC Article 430.

Free Tool · NEC Art. 430 · Wire & Breaker Sizing · Voltage Drop
Motor Parameters
V

460 V is the most common US industrial voltage. 480 V is the nominal utility supply; motors are rated 460 V to allow for line losses.

60%75%85%95%+

Typical 3-phase induction motors: 80–90% at full load.

70%80%91%98%

NEMA Premium motors: 91–96%. Standard efficiency: 85–91%.

Circuit Protection & Voltage Drop
🔌

NEC 430.52: Inverse-time breakers up to 250% FLC to handle starting inrush.

SF
📏 ft

Distance from panel to motor. NEC recommends ≤3% voltage drop on branch circuits.

Results

Enter motor specs
then hit Calculate

How 3-Phase Motor Sizing Works

Sizing a 3-phase motor circuit requires four steps per NEC Article 430: calculate full-load current (FLC), size conductors at 125% FLC, size the breaker, and set the overload relay. Use NEC Table 430.250 FLC for conductors and breakers, and nameplate FLA for the overload relay only.

1 Full-Load Current

The formula calculates FLA from kW, voltage, efficiency, and power factor. For conductor and breaker sizing, always use NEC Table 430.250 — values are intentionally conservative.

FLA (3φ) = (kW × 1000) ÷ (√3 × V × PF × η) √3 = 1.732

2 Wire Sizing (430.22)

Branch circuit conductors must be sized at minimum 125% of NEC FLC. For 10 HP / 460V: 14 A × 1.25 = 17.5 A → #12 AWG copper (20 A rated).

Min. Ampacity = NEC FLC × 1.25 Select AWG from NEC Table 310.16 (75°C Cu column)

3 Breaker Sizing (430.52)

Breakers are oversized to handle starting inrush (5–8× FLC). NEC 430.52 allows inverse-time breakers up to 250% of NEC FLC. Next standard size up is permitted.

Max Breaker (ITCB) = NEC FLC × 250% Standard sizes (240.6): 15,20,25,30,35,40, 45,50,60,70,80,90, 100,125,150,175,200A

4 Overload & VDrop

Overload (NEC 430.32) uses nameplate FLA — 125% for SF≥1.15, 115% for SF=1.0. Voltage drop check: ≤3% on branch circuit recommended.

OL Relay (SF≥1.15): Nameplate FLA × 125% VD (3φ) = √3 × I × R × L/1000

Pro Tip — NEC Table vs. NameplateUse NEC Table 430.250 FLC for conductors (430.22) and breakers (430.52). Use motor nameplate FLA for overload relay (430.32). Never cross-use these values. Always have a licensed electrician verify all motor circuit designs before installation.

NEC Table 430.250 — 3-Phase AC Motor Full-Load Currents

Full-load currents from NEC Table 430.250 for induction-type squirrel cage motors. Required for conductor and overcurrent device sizing per NEC 430.6(A)(1).

HP208 V230 V460 V575 VMin. Wire (Cu)Max. Breaker
1/22.42.21.10.9#14 AWG15 A
14.64.22.11.7#14 AWG15 A
27.56.83.42.7#14 AWG15 A
516.715.27.66.1#14 AWG20 A
10Common30.828.014.011.0#12 AWG35 A
2574.868.034.027.0#8 AWG90 A
50Heavy14313065.052.0#4 AWG175 A
100Large27324812499.0#1 AWG300 A
2005284802401924/0 AWG600 A
10 HP
460V FLC14 A
Min. Wire#12 AWG
Max. Breaker35 A
25 HP
460V FLC34 A
Min. Wire#8 AWG
Max. Breaker90 A
50 HP
460V FLC65 A
Min. Wire#4 AWG
Max. Breaker175 A

AWG Copper Wire Ampacity — 75°C (NEC Table 310.16)

#14
15 A
≤ 2 HP / 460V
#12
20 A
≤ 10 HP / 460V
#10
30 A
≤ 20 HP / 460V
#8
50 A
≤ 30 HP / 460V
#6
65 A
≤ 40 HP / 460V
#4
85 A
≤ 50 HP / 460V
#3
100 A
≤ 75 HP / 460V
#2
115 A
Medium load
#1
130 A
≤ 100 HP / 460V
2/0
175 A
Medium-large
3/0
200 A
≤ 150 HP / 460V
4/0
230 A
≤ 200 HP / 460V

Frequently Asked Questions

NEC 430.52 permits inverse-time breakers up to 250% of NEC FLC to handle motor startup inrush (5–8× FLC). The wire is protected by the overload relay (continuous overcurrent) and the breaker handles true short circuits. Wire ampacity must still be ≥125% FLC per NEC 430.22.
FLC = NEC Table 430.250 values — use for conductor sizing (430.22) and breaker sizing (430.52). FLA = motor nameplate — use for overload relay (430.32) only. Never cross-use these values.
480V is the nominal utility supply. Motors are rated 460V to account for voltage drop in distribution. Always use the 460V column of NEC Table 430.250 for 480V systems.

Estimates for planning only. Always size per NEC Article 430 and local codes. Always have a licensed electrician perform final design and installation. © TWC Industrial

Updated 2026 · NEC Art. 430 · Free to Use
Scroll to Top