3-Phase Power & Motor Sizing Calculator
Calculate required amperage, wire size (AWG), and breaker size for 3-phase industrial motors. Includes voltage drop check for long cable runs. Based on NEC Article 430.
Free Tool · NEC Art. 430 · Wire & Breaker Sizing · Voltage Drop460 V is the most common US industrial voltage. 480 V is the nominal utility supply; motors are rated 460 V to allow for line losses.
Typical 3-phase induction motors: 80–90% at full load.
NEMA Premium motors: 91–96%. Standard efficiency: 85–91%.
NEC 430.52: Inverse-time breakers up to 250% FLC to handle starting inrush.
Distance from panel to motor. NEC recommends ≤3% voltage drop on branch circuits.
Enter motor specs
then hit Calculate
How 3-Phase Motor Sizing Works
Sizing a 3-phase motor circuit requires four steps per NEC Article 430: calculate full-load current (FLC), size conductors at 125% FLC, size the breaker, and set the overload relay. Use NEC Table 430.250 FLC for conductors and breakers, and nameplate FLA for the overload relay only.
1 Full-Load Current
The formula calculates FLA from kW, voltage, efficiency, and power factor. For conductor and breaker sizing, always use NEC Table 430.250 — values are intentionally conservative.
2 Wire Sizing (430.22)
Branch circuit conductors must be sized at minimum 125% of NEC FLC. For 10 HP / 460V: 14 A × 1.25 = 17.5 A → #12 AWG copper (20 A rated).
3 Breaker Sizing (430.52)
Breakers are oversized to handle starting inrush (5–8× FLC). NEC 430.52 allows inverse-time breakers up to 250% of NEC FLC. Next standard size up is permitted.
4 Overload & VDrop
Overload (NEC 430.32) uses nameplate FLA — 125% for SF≥1.15, 115% for SF=1.0. Voltage drop check: ≤3% on branch circuit recommended.
Pro Tip — NEC Table vs. NameplateUse NEC Table 430.250 FLC for conductors (430.22) and breakers (430.52). Use motor nameplate FLA for overload relay (430.32). Never cross-use these values. Always have a licensed electrician verify all motor circuit designs before installation.
NEC Table 430.250 — 3-Phase AC Motor Full-Load Currents
Full-load currents from NEC Table 430.250 for induction-type squirrel cage motors. Required for conductor and overcurrent device sizing per NEC 430.6(A)(1).
| HP | 208 V | 230 V | 460 V | 575 V | Min. Wire (Cu) | Max. Breaker |
|---|---|---|---|---|---|---|
| 1/2 | 2.4 | 2.2 | 1.1 | 0.9 | #14 AWG | 15 A |
| 1 | 4.6 | 4.2 | 2.1 | 1.7 | #14 AWG | 15 A |
| 2 | 7.5 | 6.8 | 3.4 | 2.7 | #14 AWG | 15 A |
| 5 | 16.7 | 15.2 | 7.6 | 6.1 | #14 AWG | 20 A |
| 10Common | 30.8 | 28.0 | 14.0 | 11.0 | #12 AWG | 35 A |
| 25 | 74.8 | 68.0 | 34.0 | 27.0 | #8 AWG | 90 A |
| 50Heavy | 143 | 130 | 65.0 | 52.0 | #4 AWG | 175 A |
| 100Large | 273 | 248 | 124 | 99.0 | #1 AWG | 300 A |
| 200 | 528 | 480 | 240 | 192 | 4/0 AWG | 600 A |
AWG Copper Wire Ampacity — 75°C (NEC Table 310.16)
Frequently Asked Questions
Estimates for planning only. Always size per NEC Article 430 and local codes. Always have a licensed electrician perform final design and installation. © TWC Industrial
Updated 2026 · NEC Art. 430 · Free to Use